<초록>
Recently, indoor air quality (IAQ) has been one of the major concerns of people. Indoor parking lots are subject to be exposed to high concentrations of air pollutants emitted from vehicles. This study was performed to investigate indoor air quality (IAQ) at indoor parking lots. Sampling sites were selected 5 indoor parking lots. Target indoor air quality parameters include a number of criteria pollutants such PM10, CO, CO2, and HCHO. In addition, a variation of IAQ according to ventilation system operating was measured at C site (underground parking lot). In general, all pollutants were maintained below indoor air quality maintenance standards. The indoor air quality at indoor parking lots was affected by the availability of the ventilation facility and their operation frequency. At the underground parking lot (C site) with ventilation system, TVOC concentration according to ventilation system operating were found to be lower operating (488.2 ${\mu}g/m^3$) than non-operating (1,401.2 ${\mu}g/m^3$).
<목차>
목차
실내주차장의 실내공기질 농도특성 및 환기에 의한 저감효과 / 박정호 1
[요약] 1
I. 서론 2
II. 연구방법 2
1. 연구대상 2
2. 시료채취 및 분석방법 4
III. 결과 5
1. 각 실내주차장의 농도 비교 5
2. 환기설비 가동 유무에 따른 농도 특성 5
IV. 고찰 5
V. 결론 6
Acknowledgment 7
REFERENCES 7
습니다.